Water Purification |
| GROM Series for Residential and Commercial Use |
| Destructor Medium Series for 50 to 315 GPM |
| Destructor Large Series for 100 to 1600 GPM |
| Liquid Sugar and Thin Film |
The U.S. Public Health Services has published criteria stating the acceptability of ultraviolet disinfecting units is contingent on imparting doses of 16,000 mw/sec/cm2. All Fuller units more than double this dosage.
The GROM Series is designed for commercial uses and range from 7 to 50 gpm. Chambers are sealed on both ends and come with a port that can act as a drain, site port or UV monitor port.
High intensity ultraviolet lamps rated for over 9000 hours continuous use.
Maximum operating pressure
150 PSIG. Test pressure 200 PSIG.
Warranty:
Vessel: 5 Years
Electronics: 1 Year
|
Construction
|
Accessories
|
| Unit | GPM Fresh Water | LPM | Inlet/ Outlet Size | Amps | Dimensions |
| FGR- 07 | 7 | 27 | 3/4" | 14 | 21" x 6" x 6" |
| FGR- 10 | 10 | 38 | 3/4" | 25 | 21" x 6" x 6" |
| FGR- 15 | 15 | 57 | 3/4" | 44 | 40" x 6" x 6" |
| FGR- 30 | 30 | 114 | 1.5" | 88 | 40" x 8" x 8" |
| FGR- 40 | 40 | 152 | 1.5"/ 2" | 120 | 40" x 8" x 8" |
| FGR- 50 | 50 | 189 | 2" | 160 | 40" x 8" x 8" |
Back to Top

Well suited for applications such as:
|
The medium series units use 30" UVC lamps.
| Standard Fixtures | Horizontal / Vertical |
Optional Equipment |
| 150 PSI Operating Pressure |
Yes/ Yes |
UV Monitoring |
| Stainless Steel |
Yes/ Yes |
Tri Clamp Fittings |
| Electro polished, Passivated | Yes/ Yes | Temperature Monitor |
| Remote NEMA 4 Enclosure | Yes/ Yes | Manual Quartz Wiper |
| Electronic Ballast | Yes/ Yes | Temperature Shutoff |
| Visual Lamp Out Alarm | Yes/ Yes | Automatic Quartz Wiper |
| Running Time Meter | Yes/ Yes | Modified for Outdoor Use |
| Removable Heads | Yes/ Yes | Skid Mounted |
| Adjustable Mounting Legs | Yes/ Yes | |
| Adjustable Junction Box | Yes/ Yes | |
| Site Port | Yes/ Yes | |
| Drain Port | Yes/ Yes |
Back to Top
Full- L Units Industrial Long Lamp

The Destructor Large Series uses 60" lamps.
| Standard Features | Optional Equipment |
| 150 PSI Operating Pressure | UV Monitoring |
| 316 Electro polished and Passivated Stainless Steel | Tri Clamp Fittings |
| Remote NEMA 4 Enclosure | Temperature Monitoring with Cutoff |
| Electronic Ballast | Temperature Shutoff |
| Visual Lamp Out Alarm | Manual or Automatic Quartz Wipers |
| ersRunning Time Meter | Explosion Proof Enclosures |
| Removable Heads | Modified for Outdoor Use |
| Sanitary Fittings | |
| Adjustable Mounting Legs | Skid Mounted |
| Adjustable Junction Box | |
| Site Port | |
| Fan Cooled | |
| Drain Port |